Cooling Tower Controller (CTC)

The CTC Cooling Tower Controller enables automatic bleed off of excessive total dissolved solids and the addition of Inhibitor and Biocide chemicals. This is a practical and economical way to solve cooling tower problems. A sample is drawn from the cooling tower water and diverted through a sampling manifold.

1.CONDUCTIVITY. A conductivity reading is taken - when this reading is higher than the level set, the auxiliary output opens a solenoid valve drawing off polluted water from the cooling tower. This solenoid valve will close when the conductivity value is equal to the set point.

2.INHIBITOR. An Inhibitor dosing pump for the re-integration of make up water is connected to a water meter with pulse emitter.

3. BIOCIDE. The Biocide dosing pump is time controlled and is activated by a daily/weekly electronic timer.

PRINCIPAL TECHNICAL DATA

Standard power supply: 230Vac, 50-60Hz single phase.
Upon request:
110Vac, 240Vac.
Housing: ABS with polycarbonate transparent cover.
Protection: IP65.
Weight:
6 Kg.
Overall dimensions:

300mm x 310mm x 180mm.
Microprocessor Conductivity Meter.

Measuring range: 0-2.000 or 0-20.000 mS. 2 Set point adjustment.
L.E.D. indicators:
inhibitor pump active; auxiliary output active.
Temperature Compensation: 0-100°C (Automatic compensation available upon request).
Relay output: 230V; 240V; 110V, 5A resistive load.
Repeatability: 0.1%.
Resolution:
10 mS (0-20.000) 1 mS (0-2.000).
Conductivity probe:
1/2" Gm, in-line type, 3m moulded cable.
CD probe material: PTFE body with Stainless Steel electrodes.
Temperature range: 0-100°C.

Biocide Pump controlled by a timer

Max flow and pressure: 5 l/h @ 10 bar.
Program setting: daily, weekly, reset.
Stroke length: fixed.
Pulse frequency:
max 100 per minute.
Suction height:1.5 m.
Comprised of:
1 off flexible PVC suction hose, transparent crystal type, length 2m; 1 off semi-rigid polyethylene hose, length 2m; 1 injection valve; 1 bottom filter

Inhibitor pump

Max flow: 10 l/h @ 5 bar.
Stroke length:
fixed.
Pulse frequency:
max 100 per minute.
Suction height:
1.5 m.
Comprised of:
1 off flexible PVC suction hose, transparent crystal type, length 2m; 1 off semi-rigid polyethylene hose, length 2m; 1 injection valve; 1 bottom filter.

 

Cooling Tower Controller Pool Guard 1 Pool Guard 2
Pool Top Guard   Chlorosystem

Back
Contact US

PLEASE NOTE WE ARE NOT THE MANUFACTURERS OF THE ABOVE BRAND. CENTRAL PUMPS LTD IS AN INDEPENDENT PUMP DISTRIBUTOR.

  We Ship World-wide

Water Pumps, Chemical Pumps, Process Pumps, Barrel Pumps, Drum Pumps, Sump Pumps, Cellar Pumps, Sewage Pumps, Packaged Pumping Stations, Marine Pumps, Hygienic Pumps, Food Pumps, Oil Pumps, Grease Pumps, Sea Water Pumps, Well Pumps, Borehole Pumps, Centrifugal Pumps, Gear Pumps, Vane Pumps, Submersible Pumps, Diaphragm Pumps, Piston Pumps, Plunger Pumps, Multistage Pumps, Flexible Impeller Pumps, Oscillating Piston Pumps, Helical Rotor Pumps, Progressive Cavity Pumps, Hand Pumps, Rotary Lobe Pumps, Screw Pumps, Peristaltic Pumps, Hose Pumps, Tube Pumps, Self-Priming Pumps, Turbine Pumps, Split Casing Pumps, Peripheral Pumps, Biodiesel Pumps, Rainwater Harvesting Units, Flood Water Pumps, Cellar Pumps, Sump Pumps, submersible pumps